Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 126

The location of fire alarm signal receiving switchboard shall meet the following requirements:1.Fire alarm signal receiving switchboard shall be located in watchroom or other populated places. Where a disaster prevention center is set up, the switchboard shall be located in the center.2.May not be exposed in direct sunshine.3.Inclination shall be avoided and the shell shall be earthed.4.The operating switch of wall-mounting switchboard shall be 0.8m~1.5m high from the floor (0.6~1.5m for seat type)
中文原文 各類場所消防安全設備設置標準第126條
火警受信總機之位置,依下列規定裝置:
一、裝置於值日室等經常有人之處所。
但設有防災中心時,設於該中心。
二、裝置於日光不直接照射之位置。
三、避免傾斜裝置,其外殼應接地。
四、壁掛型總機操作開關距離樓地板面之高度,在零點八公尺(座式操作者,為零點六公尺)以上一點五公尺以下。