Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 88
Where gas-actuation is provided in CO2 or Inert Gas fire extinguishing systems, the following provisions shall be observed:1.Container of actuation gas shall be able to endure a pressure of 250kgf/cm2 or 25Mpa.2.Container of actuation gas shall have a volume of at least 1 liter; weight of the contained CO2 shall be at least 0.6kg, and the filling ratio should be at least 1.5.3.Safety device and valve for container of actuation gas shall comply with CNS 11176 specifications or shall have equivalent or better performance approved by the central authorities.4.Container of actuation gas shall not be used as auto closing device for the protected area at the same time.
中文原文 各類場所消防安全設備設置標準第88條
二氧化碳及惰性氣體滅火設備使用氣體啟動者,依下列規定設置:
一、啟動用氣體容器能耐每平方公分二百五十公斤或25MPa之壓力。
二、啟動用氣體容器之內容積應有一公升以上,其所儲存之二氧化碳重量在零點六公斤以上,且其充填比在一點五以上。
三、啟動用氣體容器之安全裝置及容器閥符合CNS一一一七六規定,或經中央主管機關認可具同等性能以上者。
四、啟動用氣體容器不得兼供防護區域之自動關閉裝置使用。
一、啟動用氣體容器能耐每平方公分二百五十公斤或25MPa之壓力。
二、啟動用氣體容器之內容積應有一公升以上,其所儲存之二氧化碳重量在零點六公斤以上,且其充填比在一點五以上。
三、啟動用氣體容器之安全裝置及容器閥符合CNS一一一七六規定,或經中央主管機關認可具同等性能以上者。
四、啟動用氣體容器不得兼供防護區域之自動關閉裝置使用。