Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 36
The capacity of indoor fire hydrant equipments shall be not less than the quantity of all the fire hydrants on the floor that has the most indoor fire hydrants continuously discharging for 20 minutes. However, if the total number of fire hydrants on the floor is more than 2, then 2 shall be used as the total number.Where fire water is used mixed together with common water, necessary measures shall be taken to ensure the capacity of the former water source are in the effective range.Water source for fire extinguisher may be equipped together with water sources for other fire extinguishing equipments, but the total capacity shall be not less than the sum of the necessary water quantity required by fire extinguishing equipments.
中文原文 各類場所消防安全設備設置標準第36條
室內消防栓設備之水源容量,應在裝置室內消防栓最多樓層之全部消防栓繼續放水二十分鐘之水量以上。
但該樓層內,全部消防栓數量超過二支時,以二支計算之。
消防用水與普通用水合併使用者,應採取必要措施,確保前項水源容量在有效水量範圍內。
第一項水源得與本章所列其他滅火設備水源併設。
但其總容量應在各滅火設備應設水量之合計以上。
但該樓層內,全部消防栓數量超過二支時,以二支計算之。
消防用水與普通用水合併使用者,應採取必要措施,確保前項水源容量在有效水量範圍內。
第一項水源得與本章所列其他滅火設備水源併設。
但其總容量應在各滅火設備應設水量之合計以上。