Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 33
Upon completion of installing indoor fire hydrant equipments, pressurization test shall be made under a test pressure not less than 1.5 times the total closed pumping lift of the pressurization and driving device. If leakage doesn’t occur after the test pressure lasts for two hours, the equipments shall be regarded as qualified.
中文原文 各類場所消防安全設備設置標準第33條
室內消防栓設備之消防立管管系竣工時,應做加壓試驗,試驗壓力不得小於加壓送水裝置全閉揚程一點五倍以上之水壓。
試驗壓力以繼續維持二小時無漏水現象為合格。