Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 176
Wiring of all emergency lighting equipment except inbuilt storage battery type, shall comply to the following requirements:1.Lighting equipment shall be directly connected to the divided distribution circuit; no sockets or switches shall be attached therewith.2.In terms of the power supply circuit of emergency lighting lamps, its wiring shall have flame-resistant protection pursuant to the requirement stated in Article 235. However, heat-resistant protection may be adopted when the ceiling and its base materials are constructed using inflammable materials.
中文原文 各類場所消防安全設備設置標準第176條
緊急照明設備除內置蓄電池式外,其配線依下列規定:
一、照明器具直接連接於分路配線,不得裝置插座或開關等。
二、緊急照明燈之電源回路,其配線依第二百三十五條規定施予耐燃保護。
但天花板及其底材使用不燃材料時,得施予耐熱保護。
一、照明器具直接連接於分路配線,不得裝置插座或開關等。
二、緊急照明燈之電源回路,其配線依第二百三十五條規定施予耐燃保護。
但天花板及其底材使用不燃材料時,得施予耐熱保護。