Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 124
Flame type detector shall comply with the following provisions:1.Detector shall be installed on ceiling, floorslabs, or wall.2.The nominal supervising distance of a detector shall cover the space within 1.2m from the floor surface.3.Detector may not be installed at a location where there is any obstacle encumbering the detector from detecting the occurrence of fire.4.Detector may not be located directly under the sunshine, unless lightproof function is provided to prevention detection from being encumbered.
中文原文 各類場所消防安全設備設置標準第124條
火焰式探測器,依下列規定設置:
一、裝設於天花板、樓板或牆壁。
二、距樓地板面一點二公尺範圍內之空間,應在探測器標稱監視距離範圍內。
三、探測器不得設在有障礙物妨礙探測火災發生處。
四、探測器設在無日光照射之處。
但設有遮光功能可避免探測障礙者,不在此限。