Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 116
It is allowable that detectors are not installed in the following occasions:1.The mounting surface is higher than 20m (except for flame type detectors).2.Places where fire detecting becomes ineffective due to airflow.3.Toilet, water closet or bathroom.4.Cold stores where automatic temperature regulating device that is able to detect the occurrence of fire in the beginning has been equipped.5.Cashbox where the main construction is fireproof and the opening is equipped with fireproof door that can resist the fire at least one hour.6.Above water surface of indoor swimming pool, or ice surface of skating ground.7.Processing grounds of inflammable stones or metals, where flammable substances are not stored or processed.8.Other places designated by the central regulating authority.
中文原文 各類場所消防安全設備設置標準第116條
下列處所得免設探測器:
一、探測器除火焰式外,裝置面高度超過二十公尺者。
二、外氣流通無法有效探測火災之場所。
三、洗手間、廁所或浴室。
四、冷藏庫等設有能早期發現火災之溫度自動調整裝置者。
五、主要構造為防火構造,且開口設有具一小時以上防火時效防火門之金庫。
六、室內游泳池之水面或溜冰場之冰面上方。
七、不燃性石材或金屬等加工場,未儲存或未處理可燃性物品處。
八、其他經中央主管機關指定之場所。
一、探測器除火焰式外,裝置面高度超過二十公尺者。
二、外氣流通無法有效探測火災之場所。
三、洗手間、廁所或浴室。
四、冷藏庫等設有能早期發現火災之溫度自動調整裝置者。
五、主要構造為防火構造,且開口設有具一小時以上防火時效防火門之金庫。
六、室內游泳池之水面或溜冰場之冰面上方。
七、不燃性石材或金屬等加工場,未儲存或未處理可燃性物品處。
八、其他經中央主管機關指定之場所。