Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 115
Mounting position of detector shall comply with the following provisions:1.Where the ceiling is equipped with an air outlet, the mounting position shall be 1.5m or farther away from the outlet with exceptions of flame type, differential distributed and photoelectrical separated type.2.Where there is an air outlet on the wall, the mounting position shall be 1.5m or farther away from the outlet, unless the distance between the outlet and the ceiling is not less than 1m.3.Where the ceiling is equipped with an air outlet or inlet, smoke detector shall be equipped within 1m around the outlet or inlet.4.In principle, topical detectors shall be mounted around the center of the detected area.5.Topical detectors may not incline 45°or more with exception of flame type.
中文原文 各類場所消防安全設備設置標準第115條
探測器之裝置位置,依下列規定:
一、天花板上設有出風口時,除火焰式、差動式分布型及光電式分離型探測器外,應距離該出風口一點五公尺以上。
二、牆上設有出風口時,應距離該出風口一點五公尺以上。
但該出風口距天花板在一公尺以上時,不在此限。
三、天花板設排氣口或回風口時,偵煙式探測器應裝置於排氣口或回風口周圍一公尺範圍內。
四、局限型探測器以裝置在探測區域中心附近為原則。
五、局限型探測器之裝置,不得傾斜四十五度以上。
但火焰式探測器,不在此限。
一、天花板上設有出風口時,除火焰式、差動式分布型及光電式分離型探測器外,應距離該出風口一點五公尺以上。
二、牆上設有出風口時,應距離該出風口一點五公尺以上。
但該出風口距天花板在一公尺以上時,不在此限。
三、天花板設排氣口或回風口時,偵煙式探測器應裝置於排氣口或回風口周圍一公尺範圍內。
四、局限型探測器以裝置在探測區域中心附近為原則。
五、局限型探測器之裝置,不得傾斜四十五度以上。
但火焰式探測器,不在此限。