Standards for Establishing Places for Manufacturing, Storing, Processing Public Hazardous Substances and Flammable Pressurized Gases, and Regulations on Safety Control of such Places Article 69
The location, construction, equipment, and safety management of flammable pressurized gas processing place shall meet the following requirements:1.The trading place:(1)It shall be located on the ground floor of a building.(2)The area of the building used for trading shall meet the following:i.The walls shall be constructed from fireproof materials or non-flammable materials. However, the partitioning walls used to separate this area from other areas of the building shall be made from fireproof construction.ii.The beams and ceilings shall be constructed from non-flammable materials.iii.In cases where there is an upper floor, its floor shall be made from fireproof construction. In the absence of an upper floor, the roof shall be built with fireproof construction or non-flammable materials.(3)Any fire source is forbidden.(4)A gas leak alarm shall be installed when the gas storage capacity is greater than 80kg.2.The container inspection place:(1)It shall meet the requirements set forth in Article 68.1, 68.2.(2)A gas leak alarm shall be installed in facilities where there is potential leakage possibility of liquefied petroleum gas.(3)An automatic emergency shutoff device shall be installed in places that use gas appliance.(4)Any fire source is forbidden except for when it is required for inspection.
中文原文 公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法第69條
可燃性高壓氣體處理場所之位置、構造、設備及安全管理,應符合下列規定:
一、販賣場所:
(一)應設於建築物之地面層。
(二)建築物供販賣場所使用部分,應符合下列規定:1.牆壁應為防火構造或不燃材料建造。
但與建築物其他使用部分之隔間牆,應為防火構造。
2.樑及天花板應以不燃材料建造。
3.其上有樓層者,上層之地板應為防火構造;其上無樓層者,屋頂應為防火構造或以不燃材料建造。
(三)不得使用火源。
(四)儲氣量八十公斤以上者,應設置氣體漏氣警報器。
二、容器檢驗場所:
(一)應符合前款第一目及第二目規定。
(二)有洩漏液化石油氣之虞之設施,應設置氣體漏氣警報器。
(三)使用燃氣設備者,應連動緊急遮斷裝置。
(四)不得使用火源。
但因檢驗作業需要者,不在此限。
一、販賣場所:
(一)應設於建築物之地面層。
(二)建築物供販賣場所使用部分,應符合下列規定:1.牆壁應為防火構造或不燃材料建造。
但與建築物其他使用部分之隔間牆,應為防火構造。
2.樑及天花板應以不燃材料建造。
3.其上有樓層者,上層之地板應為防火構造;其上無樓層者,屋頂應為防火構造或以不燃材料建造。
(三)不得使用火源。
(四)儲氣量八十公斤以上者,應設置氣體漏氣警報器。
二、容器檢驗場所:
(一)應符合前款第一目及第二目規定。
(二)有洩漏液化石油氣之虞之設施,應設置氣體漏氣警報器。
(三)使用燃氣設備者,應連動緊急遮斷裝置。
(四)不得使用火源。