Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 68

Drainage equipments in indoor parking areas equipped with water spray fire extinguisher shall comply with the following provisions:1.The ground of parking area shall have a slope gradient of more than 2%.2.Parking slots except the proportion toward the driveway shall be equipped with 10cm or higher boundary barrier or boundary ditch with a depth up to 10cm and width over 10cm, which shall be connected with drainage.3.Fire extinguishing pit shall be provided with oil-water separator, and located in place where it is difficult for fire to reach.4.Drainage ditch shall be equipped with collecting pipes and in the center or the two sides of driveway and connected to the fire extinguishing pit.5.The size and slope gradient of drainage ditch and collecting pipe shall ensure the maximum capacity of the pressurization and driving device can be discharged effectively.
中文原文 各類場所消防安全設備設置標準第68條
裝置水霧滅火設備之室內停車空間,其排水設備應符合下列規定:
一、車輛停駐場所地面作百分之二以上之坡度。
二、車輛停駐場所,除面臨車道部分外,應設高十公分以上之地區境界堤,或深十公分寬十公分以上之地區境界溝,並與排水溝連通。
三、滅火坑具備油水分離裝置,並設於火災不易殃及之處所。
四、車道之中央或二側設置排水溝,排水溝設置集水管,並與滅火坑相連接。
五、排水溝及集水管之大小及坡度,應具備能將加壓送水裝置之最大能力水量有效排出。