Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 53
Deluge valve of open type automatic sprinkler system shall be pursuant to the following provisions:1.Each discharge area shall be equipped one.2.The secondary side piping of all-around relief valve shall be equipped with testing device, which is able to test the motion of the valve when water is not discharge in this area.3.The pressure endured by deluge valve shall be not more than the maximum working pressure.
中文原文 各類場所消防安全設備設置標準第53條
開放式自動撒水設備之一齊開放閥應依下列規定設置:
一、每一放水區域設置一個。
二、一齊開放閥二次側配管裝設試驗用裝置,在該放水區域不放水情形下,能測試一齊開放閥之動作。
三、一齊開放閥所承受之壓力,在其最高使用壓力以下。
一、每一放水區域設置一個。
二、一齊開放閥二次側配管裝設試驗用裝置,在該放水區域不放水情形下,能測試一齊開放閥之動作。
三、一齊開放閥所承受之壓力,在其最高使用壓力以下。