Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 28
The installation of smoke exhaust equipment is required for the following places:1.Places prescribed in Article 12 Subparagraph 1 and Subparagraph 5, Item (3), having a total floor area of at least 500 m2.2.Living rooms having a floor area measuring at least 100 m2, where area of the effective ventilation located within 80-cm under the ceiling is less than 2% of the total floor area of the living room.3.A non-opening story having a floor area measuring at least 1,000 m2.4.Places prescribed in Article 12 Subparagraph 1, Item (1) and assembly halls prescribed in Item (2) containing a stage measuring at least 500m2.5.Where vestibules of special refuge stairways or emergency elevators are installed pursuant to the requirements of the Building Technical Regulations.A separate assessment shall be permitted in the event of additions, reconstructions, or alterations, where the floor area of the aforesaid places are within a building structure compartmented by one- hour fire resistance rated fire walls, fire separation assemblies, such as fire doors and fire windows, which are regularly kept closed, and fire resistance rated floor. The fire separation assemblies installed shall have a thermal insulation capacity of at least one hour.
中文原文 各類場所消防安全設備設置標準第28條
下列場所應設置排煙設備:
一、供第十二條第一款及第五款第三目所列場所使用,樓地板面積合計在五百平方公尺以上。
二、樓地板面積在一百平方公尺以上之居室,其天花板下方八十公分範圍內之有效通風面積未達該居室樓地板面積百分之二者。
三、樓地板面積在一千平方公尺以上之無開口樓層。
四、供第十二條第一款第一目所列場所及第二目之集會堂使用,舞臺部分之樓地板面積在五百平方公尺以上者。
五、依建築技術規則應設置之特別安全梯或緊急昇降機間。
前項場所之樓地板面積,在建築物以具有一小時以上防火時效之牆壁、平時保持關閉之防火門窗等防火設備及各該樓層防火構造之樓地板區劃,且防火設備具一小時以上之阻熱性者,增建、改建或變更用途部分得分別計算。
一、供第十二條第一款及第五款第三目所列場所使用,樓地板面積合計在五百平方公尺以上。
二、樓地板面積在一百平方公尺以上之居室,其天花板下方八十公分範圍內之有效通風面積未達該居室樓地板面積百分之二者。
三、樓地板面積在一千平方公尺以上之無開口樓層。
四、供第十二條第一款第一目所列場所及第二目之集會堂使用,舞臺部分之樓地板面積在五百平方公尺以上者。
五、依建築技術規則應設置之特別安全梯或緊急昇降機間。
前項場所之樓地板面積,在建築物以具有一小時以上防火時效之牆壁、平時保持關閉之防火門窗等防火設備及各該樓層防火構造之樓地板區劃,且防火設備具一小時以上之阻熱性者,增建、改建或變更用途部分得分別計算。