Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 223

Dry powder Fire Extinguishing Systems are applicable to provisions of Arti-cle 98 through Article 111. For within the range of a protected area, or when the protected subject is for storing or processing public hazard objects, dosage shall be calculated by multiplying the result of Article 99 with agent coefficient tabulated in Article 222, Paragraph 3. For public hazard objects or agent coefficient not tabulated in Article 222. Paragraph 3, use design co-efficient certified by the central authority for the calculation.
中文原文 各類場所消防安全設備設置標準第223條
乾粉滅火設備準用第九十八條至第一百十一條規定。
但於防護區域內或防護對象係為儲存、處理之公共危險物品,依第二百二十二條第三項表列滅火藥劑之係數乘以第九十九條所算出之量。
第二百二十二條第三項未表列之公共危險物品或係數,依中央主管機關認可之設計係數值核算之。