Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 192-1

The disaster prevention center ,central management room or duty room shall install disaster monitoring and controlling system to monitor or operate the following fire safety equipment:1.The receiver of the automatic fire alarm system.2.The receiver of the automatic gas leakage fire alarm system.3.The speakers and operating devices of the emergency broadcasting equipment.4.The pressurized water supply device of the standpipe and hose system, and the communication device at the fire department connection of the system.5.Emergency generator.6.The smoke detectors located on the constantly open fire doors.7.The pressurized water supply devices of the hydrant, sprinkler, foam, water spray, and other fire-suppression equipment.8.The dry power and carbon dioxide fire-suppression equipment.9.The smoke exhaust equipment.The emergency power supply of the integrated operation device of the disaster monitoring and controlling system shall be in accordance with the provisions of Article 38, and its power supply capacity shall be available for its effective operation for more than two hours.
中文原文 各類場所消防安全設備設置標準第192-1條
防災監控系統綜合操作裝置應設置於防災中心、中央管理室或值日室等經常有人之處所,並監控或操作下列消防安全設備:
一、火警自動警報設備之受信總機。
二、瓦斯漏氣火警自動警報設備之受信總機。
三、緊急廣播設備之擴大機及操作裝置。
四、連結送水管之加壓送水裝置及與其送水口處之通話連絡。
五、緊急發電機。
六、常開式防火門之偵煙型探測器。
七、室內消防栓、自動撒水、泡沫及水霧等滅火設備加壓送水裝置。
八、乾粉、惰性氣體及鹵化烴等滅火設備。
九、排煙設備。
防災監控系統綜合操作裝置之緊急電源準用第三十八條規定,且其供電容量應供其有效動作二小時以上。