Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 190
Smoke Exhaust Device can be exempted at the following places:1.Floors located below (including) the 10th floor of the building (except the basement) for non-living room used parts that comply with any of the following provisions:(1)Ceiling and indoor walls decorated with Grade I fire-resistant materials, and separated with a fire door or window that can resist the fire for at least half an hour.(2)The floor area is less than 100m2, and separated by smoke-prevention walls.2.Floors located below (including) the 10th floor of the building (except the basement) for living room used comply with any of the following provisions:(1)Every 100m2 of the floor area is zoned for fire prevention with walls, fire doors & windows, and slabs of the fire prevention structure of that floor for at least 1 hour fire resistance; ceiling and surface of indoor walls are decorated with Grade I fire-resistant materials.(2)The floor area is less than 100m2, and ceiling and indoor wall surfaces and substrate are decorated with Grade I fire resistant materials.3.In levels above the 11th floor in the building, basement or underground structure (except Category A basement or underground structure), every 100m2 of the floor area is zoned for fire prevention with walls, fire doors & windows, and slabs of the fire prevention structure of that floor, for at least 1 hour fire resistance; and ceiling and indoor wall surfaces and substrates are decorated with Grade I fire resistant materials. 4.Stairway, elevator well passageway, utility shaft, storage room, washing room, toilet and other similar parts.5.Places equipped with CO2, Inert Gas, Halocarbon or dry powder fire extinguishing systems.6.Machine factory, warehouse storing nonflammable materials and other similar buildings, where the main construction is of nonflammable materials.7.Condominiums, school classrooms, school activity centers, gymnasiums, indoor skating yards and indoor swimming pools.8.Other places approved by the central authority.Fire doors and windows and other fire prevention facilities of Subparagraph 1, Item 1 of the above Paragraph shall be heat retardant for at least half an hour; those of Subparagraph 2, Item 1 and Subparagraph 3 shall be heat re-tardant for at least one hour.
中文原文 各類場所消防安全設備設置標準第190條
下列處所得免設排煙設備:
一、建築物在第十層以下之各樓層(地下層除外),其非居室部分,符合下列規定之一者:
(一)天花板及室內牆面,以耐燃一級材料裝修,且除面向室外之開口外,以半小時以上防火時效之防火門窗等防火設備區劃。
(二)樓地板面積每一百平方公尺以下,以防煙壁區劃。
二、建築物在第十層以下之各樓層(地下層除外),其居室部分,符合下列規定之一者:
(一)樓地板面積每一百平方公尺以下,以具一小時以上防火時效之牆壁、防火門窗等防火設備及各該樓層防火構造之樓地板形成區劃,且天花板及室內牆面,以耐燃一級材料裝修。
(二)樓地板面積在一百平方公尺以下,天花板及室內牆面,且包括其底材,均以耐燃一級材料裝修。
三、建築物在第十一層以上之各樓層、地下層或地下建築物(地下層或地下建築物之甲類場所除外),樓地板面積每一百平方公尺以下,以具一小時以上防火時效之牆壁、防火門窗等防火設備及各該樓層防火構造之樓地板形成區劃間隔,且天花板及室內牆面,以耐燃一級材料裝修者。
四、樓梯間、昇降機昇降路、管道間、儲藏室、洗手間、廁所及其他類似部分。
五、設有二氧化碳、惰性氣體、鹵化烴或乾粉等滅火設備之場所。
六、機器製造工廠、儲放不燃性物品倉庫及其他類似用途建築物,且主要構造為不燃材料建造者。
七、集合住宅、學校教室、學校活動中心、體育館、室內溜冰場、室內游泳池。
八、其他經中央主管機關核定之場所。
前項第一款第一目之防火門窗等防火設備應具半小時以上之阻熱性,第二款第一目及第三款之防火門窗等防火設備應具一小時以上之阻熱性。
一、建築物在第十層以下之各樓層(地下層除外),其非居室部分,符合下列規定之一者:
(一)天花板及室內牆面,以耐燃一級材料裝修,且除面向室外之開口外,以半小時以上防火時效之防火門窗等防火設備區劃。
(二)樓地板面積每一百平方公尺以下,以防煙壁區劃。
二、建築物在第十層以下之各樓層(地下層除外),其居室部分,符合下列規定之一者:
(一)樓地板面積每一百平方公尺以下,以具一小時以上防火時效之牆壁、防火門窗等防火設備及各該樓層防火構造之樓地板形成區劃,且天花板及室內牆面,以耐燃一級材料裝修。
(二)樓地板面積在一百平方公尺以下,天花板及室內牆面,且包括其底材,均以耐燃一級材料裝修。
三、建築物在第十一層以上之各樓層、地下層或地下建築物(地下層或地下建築物之甲類場所除外),樓地板面積每一百平方公尺以下,以具一小時以上防火時效之牆壁、防火門窗等防火設備及各該樓層防火構造之樓地板形成區劃間隔,且天花板及室內牆面,以耐燃一級材料裝修者。
四、樓梯間、昇降機昇降路、管道間、儲藏室、洗手間、廁所及其他類似部分。
五、設有二氧化碳、惰性氣體、鹵化烴或乾粉等滅火設備之場所。
六、機器製造工廠、儲放不燃性物品倉庫及其他類似用途建築物,且主要構造為不燃材料建造者。
七、集合住宅、學校教室、學校活動中心、體育館、室內溜冰場、室內游泳池。
八、其他經中央主管機關核定之場所。
前項第一款第一目之防火門窗等防火設備應具半小時以上之阻熱性,第二款第一目及第三款之防火門窗等防火設備應具一小時以上之阻熱性。