Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 146-5

When installed in the following occupancy, exit indicating lamps and direction indicating lamps that are not located in stairways and slopes, shall be class A or B. The face illumination of exit indicating lamps shall be not less than 20cd or possess flash function. The face illumination of the direction indicating lamps shall be not less than 25 cd. The preceding restrictions shall not apply to lamps that are installed in hallways, and that are easily recognized within effective range thereof.1. Occupancy specified in article 12.2(1), 12.3(3) or 12.5(3).2. Occupancy specified in article 12.1(1 through 5, 7) or 12.5 (1) where the floor area is greater than 1,000 square meters.3. The exit indicating lamps adopted by occupancy specified in article 12.1 (6), shall possess flash or voice indicating function.The flash or voice indicating function of exit indicating lamps as prescribed in the preceding subparagraph shall comply with the following:1. Shall be installed in main exits.2. The lamp shall be linked to automatic fire alarm system.3. When the detector installed at the location of main exits toward evacuation direction is activated, the exit indicating lamps shall stop flash or voice indicating function.Direction indicating lamps installed in stairways or slopes, shall have illuminance not less than 1 lx on the surface of the stairway or slope.
中文原文 各類場所消防安全設備設置標準第146-5條
出口標示燈及非設於樓梯或坡道之避難方向指示燈,設於下列場所時,應使用A級或B級;出口標示燈標示面光度應在二十燭光(cd)以上,或具閃滅功能;避難方向指示燈標示面光度應在二十五燭光(cd)以上。
但設於走廊,其有效範圍內各部分容易識別該燈者,不在此限:
一、供第十二條第二款第一目、第三款第三目或第五款第三目使用者。
二、供第十二條第一款第一目至第五目、第七目或第五款第一目使用,該層樓地板面積在一千平方公尺以上者。
三、供第十二條第一款第六目使用者。
其出口標示燈並應採具閃滅功能,或兼具音聲引導功能者。
前項出口標示燈具閃滅或音聲引導功能者,應符合下列規定:
一、設於主要出入口。
二、與火警自動警報設備連動。
三、由主要出入口往避難方向所設探測器動作時,該出入口之出口標示燈應停止閃滅及音聲引導。
避難方向指示燈設於樓梯或坡道者,在樓梯級面或坡道表面之照度,應在一勒克司(lx)以上。

English translation for reference only; the Chinese text prevails. Not legal advice.