Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 146-3
Exit indicating lamps shall be installed at effective indicating position which is above or close near the exits specified below:1. Exits that lead outdoors or exits of vestibules, if vestibules exist.2. Exits that lead to stairways or exits of vestibules, if vestibules exist.3. Exits from the indoor to hallways and passages that lead to exits as prescribed in the preceding two subparagraphs.4. The fire door that is installed across the fire compartment at hallways or passages that lead to exits as prescribed in the preceding subparagraph 1 and 2.Direction indicating lamps shall be installed in hallways, stairways, and passages, in compliance with the following:1. Preferably installed in turning corners.2. Be installed within effective ranges of the exit indicating lamps as prescribed in the preceding paragraph, subparagraph 1 and 2.3. Be installed at necessary locations other than places as prescribed in the preceding two subparagraphs, to cover all parts of hallways or passages in effective ranges of the direction indicating lamps.
中文原文 各類場所消防安全設備設置標準第146-3條
出口標示燈應設於下列出入口上方或其緊鄰之有效引導避難處:
一、通往戶外之出入口;設有排煙室者,為該室之出入口。
二、通往直通樓梯之出入口;設有排煙室者,為該室之出入口。
三、通往前二款出入口,由室內往走廊或通道之出入口。
四、通往第一款及第二款出入口,走廊或通道上所設跨防火區劃之防火門。
避難方向指示燈,應裝設於設置場所之走廊、樓梯及通道,並符合下列規定:
一、優先設於轉彎處。
二、設於依前項第一款及第二款所設出口標示燈之有效範圍內。
三、設於前二款規定者外,把走廊或通道各部分包含在避難方向指示燈有效範圍內,必要之地點。
一、通往戶外之出入口;設有排煙室者,為該室之出入口。
二、通往直通樓梯之出入口;設有排煙室者,為該室之出入口。
三、通往前二款出入口,由室內往走廊或通道之出入口。
四、通往第一款及第二款出入口,走廊或通道上所設跨防火區劃之防火門。
避難方向指示燈,應裝設於設置場所之走廊、樓梯及通道,並符合下列規定:
一、優先設於轉彎處。
二、設於依前項第一款及第二款所設出口標示燈之有效範圍內。
三、設於前二款規定者外,把走廊或通道各部分包含在避難方向指示燈有效範圍內,必要之地點。