Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 145-1
119 fire notification devices shall comply with the following requirements:1. They shall be installed in watch room or other usually populated places. Where a surveillance center is set up, the switchboard shall be installed in the center.2. They should provide manual and automatic actuating function.3. When setting up the remote starting device, there should be a device that can communicate with the people where the 119 fire notification device was set.4. The operation switch of the manual actuating device shall be installed at higher than 0.8m and lower than 1.5m from the ground.5. The transmitter and receiver should be set up and clearly distinguished from other intercom calls near the device.6. They shall not be installed aslant, and shockproof measures shall be taken.
中文原文 各類場所消防安全設備設置標準第145-1條
一一九火災通報裝置,依下列規定設置:
一、應具手動及自動啟動功能。
二、應設於值日室等經常有人之處所。
但設有防災中心時,應設於該中心。
三、設置遠端啟動裝置時,應設有可與設置一一九火災通報裝置場所通話之設備。
四、手動啟動裝置之操作開關距離樓地板面之高度,在零點八公尺以上一點五公尺以下。
五、裝置附近,應設置送、收話器,並與其他內線電話明確區分。
六、應避免斜裝置,並採取有效防震措施。
一、應具手動及自動啟動功能。
二、應設於值日室等經常有人之處所。
但設有防災中心時,應設於該中心。
三、設置遠端啟動裝置時,應設有可與設置一一九火災通報裝置場所通話之設備。
四、手動啟動裝置之操作開關距離樓地板面之高度,在零點八公尺以上一點五公尺以下。
五、裝置附近,應設置送、收話器,並與其他內線電話明確區分。
六、應避免斜裝置,並採取有效防震措施。