Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 105
Piping and valves of dry chemicals fire extinguishing equipments shall be equipped pursuant to the following provisions:1.Piping(1)It shall be used dedicatedly and its diameter shall be determined according to the amount of spraying amount of nozzles.(2)Steel pipe, which is complied with National Standard CNS No. 6445 and has been anti-corrosive treated or has the same or higher strength and corrosion endurance, shall be employed, but seamless steel pipe complied with National Standard CNS No. 4626, wherein the thickness or strength is the same as or higher than that of pipe number SCH40 and anticorrosive treatment like zincing etc has been made, shall be used for pressure-maintaining type when the pressure is more than 25kg/cm2 or 0.25Mpa and less than 42kg/cm2 or 4.2Mpa.(3)Where copper pipe is used, the copper pipe shall comply with National Standard CNS No. 5127 or have the same or higher strength, and be able to endure a pressure at least 1.5 times the adjustment pressure or the highest pressure.(4)Drop height between highest matching pipe and lowest matching pipe shall be less than 50m.(5)Matching pipes shall be distributed evenly so as to ensure the same spraying pressure of each nozzle when spraying at the same time.(6)Effective quakeproof steps shall be applied.2.Valves(1)Valve shall comply with National Standards CNS or have the same or higher strength and corrosion endurance, and anti-corrosion treatment shall have been made.(2)Location and direction of switch shall be marked.(3)Manual operating part of relief valve and container valve of pressurizing gas shall be located in safe and accessible places.
中文原文 各類場所消防安全設備設置標準第105條
乾粉滅火設備配管及閥類,依下列規定設置:
一、配管部分:
(一)應為專用,其管徑依噴頭流量計算配置。
(二)使用符合CNS六四四五規定,並施予鍍鋅等防蝕處理或具同等以上強度及耐蝕性之鋼管。
但蓄壓式中,壓力在每平方公分二十五公斤以上或2.5MPa以上,每平方公分四十二公斤以下或4.2MPa以下時,應使用符合CNS四六二六之無縫鋼管管號Sch40以上厚度並施予防蝕處理,或具有同等以上強度及耐蝕性之鋼管。
(三)採用銅管配管時,應使用符合CNS五一二七規定或具有同等以上強度及耐蝕性者,並能承受調整壓力或最高使用壓力的一點五倍以上之壓力。
(四)最低配管與最高配管間,落差在五十公尺以下。
(五)配管採均分為原則,使噴頭同時放射時,放射壓力為均等。
(六)採取有效之防震措施。
二、閥類部分:
(一)使用符合CNS之規定且施予防蝕處理或具有同等以上強度、耐蝕性及耐熱性者。
(二)標示開閉位置及方向。
(三)放出閥及加壓用氣體容器閥之手動操作部分設於火災時易於接近且安全之處。
一、配管部分:
(一)應為專用,其管徑依噴頭流量計算配置。
(二)使用符合CNS六四四五規定,並施予鍍鋅等防蝕處理或具同等以上強度及耐蝕性之鋼管。
但蓄壓式中,壓力在每平方公分二十五公斤以上或2.5MPa以上,每平方公分四十二公斤以下或4.2MPa以下時,應使用符合CNS四六二六之無縫鋼管管號Sch40以上厚度並施予防蝕處理,或具有同等以上強度及耐蝕性之鋼管。
(三)採用銅管配管時,應使用符合CNS五一二七規定或具有同等以上強度及耐蝕性者,並能承受調整壓力或最高使用壓力的一點五倍以上之壓力。
(四)最低配管與最高配管間,落差在五十公尺以下。
(五)配管採均分為原則,使噴頭同時放射時,放射壓力為均等。
(六)採取有效之防震措施。
二、閥類部分:
(一)使用符合CNS之規定且施予防蝕處理或具有同等以上強度、耐蝕性及耐熱性者。
(二)標示開閉位置及方向。
(三)放出閥及加壓用氣體容器閥之手動操作部分設於火災時易於接近且安全之處。