Standards for Establishing Places for Manufacturing, Storing, Processing Public Hazardous Substances and Flammable Pressurized Gases, and Regulations on Safety Control of such Places Article 22

While the location, construction and equipment of the indoor storage for Class 2 public hazardous materials other than combustible solids, or Class 4 public hazardous materials with a flash point not below 70℃ shall meet those requirements set forth in Articles 21.1~21.3, and 21.7 ~ 21.14, the warehouse of the indoor storage may be provided in a building having two or more storeys and the building shall meet the following requirements:1.The floor of the lowest story shall be at where higher than the ground and the height of each story shall not be greater than 6m;2.The total floorage shall not be greater than 1,000 m2;3.Walls, beams, pillars and floors shall be of fireproof construction, stairs shall be constructed with non-flammable materials, and no opening other than the access shall be provided to the exterior wall with the risk of fire extension; and4.No opening shall be provided to the floor on the second storey and above unless the partitioning wall in the stairway is of fireproof construction and is separated with fire doors of 30 minutes and more fire rate.
中文原文 公共危險物品及可燃性高壓氣體製造儲存處理場所設置標準暨安全管理辦法第22條
室內儲存場所儲存易燃性固體以外之第二類公共危險物品或閃火點達攝氏七十度以上之第四類公共危險物品者,其位置、構造及設備除應符合前條第一款至第三款及第七款至第十四款規定外,其儲存倉庫得設於二層以上建築物,並應符合下列規定:
一、最低層樓地板應高於地面,且各樓層高度不得超過六公尺。
二、總樓地板面積不得超過一千平方公尺。
三、牆壁、樑、柱及地板應為防火構造,樓梯應以不燃材料建造,外牆有延燒之虞者,除出入口外,不得設置開口。
四、第二層以上之地板不得設有開口。
但樓梯隔間牆為防火構造,且設有三十分鐘以上防火時效之防火門區劃分隔者,不在此限。