Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 97-4
Nozzles of Halocarbon Clean Agent Fire Extinguishing Systems shall be equipped pursuant to the following provisions:1.The nozzles shall be capable of quickly spraying the agent and evenly distributing it throughout the protected area.2.Discharge pressure of nozzle shall be at least 9kg/cm2 or 0.9Mpa for HFC-23, at least 3 kg/cm2 or 0.3Mpa for HFC-227ea or FK-5-1-12, unless otherwise approved by central authorities.3.Quantity and type of nozzles shall be determined according to flow calculation.Dosage of fire extinguishing agent calculated per the above Article shall be sprayed out at least 95% within 10 seconds.
中文原文 各類場所消防安全設備設置標準第97-4條
鹵化烴滅火設備之噴頭,依下列規定設置:
一、噴頭能使放射藥劑迅速且均勻擴散至整個防護區域。
二、噴頭之放射壓力,HFC-23為每平方公分九公斤以上或0.9Mpa以上,HFC-227ea或FK-5-1-12為每平方公分三公斤以上或0.3MPa以上。
但經中央主管機關認可者,不在此限。
三、噴頭數量及型式,依流量計算配置。
依前條所核算之滅火藥劑量,應於十秒內放射百分之九十五以上。
一、噴頭能使放射藥劑迅速且均勻擴散至整個防護區域。
二、噴頭之放射壓力,HFC-23為每平方公分九公斤以上或0.9Mpa以上,HFC-227ea或FK-5-1-12為每平方公分三公斤以上或0.3MPa以上。
但經中央主管機關認可者,不在此限。
三、噴頭數量及型式,依流量計算配置。
依前條所核算之滅火藥劑量,應於十秒內放射百分之九十五以上。