Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 96
In addition to Article 87, Paragraph 1, Subparagraph 1, Item 1, Subparagraph 2, Item 2 and Item 3, Subparagraph 3, Subparagraph 4 and Subparagraph.9, the following provisions shall be applicable to movable spraying of CO2 fire extinguishing systems:1.Valve of storage container can be switched manually at hose outlet.2.Storage containers shall be equipped separately at the hose mount.3.Red indicator shall be equipped near the storing container and labeled with “Movable CO2 Fire Extinguishing System”.4.Equipment shall be placed at locations less prone to being covered by fumes during a fire.5.The quantity of fire extinguishing agent sprayed by each nozzle shall be at least 60kg/minute at 20℃.6.Hose, nozzle and hose reel shall comply with CNS 11177 specifications. Enclosure Integrity Test
中文原文 各類場所消防安全設備設置標準第96條
二氧化碳滅火設備移動式放射方式,除依第八十七條第一項第一款第一目、第二款第二目、第三目、第三款、第四款及第九款規定辦理外,並依下列規定設置:
一、儲存容器之容器閥能在皮管出口處以手動開關者。
二、儲存容器分設於各皮管設置處。
三、儲存容器近旁設紅色標示燈及標明移動式二氧化碳滅火設備字樣。
四、設於火災時濃煙不易籠罩之處所。
五、每一具瞄子之藥劑放射量在溫度攝氏二十度時,應在每分鐘六十公斤以上。
六、皮管、噴嘴及管盤符合CNS一一一七七之規定。
一、儲存容器之容器閥能在皮管出口處以手動開關者。
二、儲存容器分設於各皮管設置處。
三、儲存容器近旁設紅色標示燈及標明移動式二氧化碳滅火設備字樣。
四、設於火災時濃煙不易籠罩之處所。
五、每一具瞄子之藥劑放射量在溫度攝氏二十度時,應在每分鐘六十公斤以上。
六、皮管、噴嘴及管盤符合CNS一一一七七之規定。