Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 65

Water source equipped under Article 64 shall be connected to water pressurization and driving device.Where fire pump is used as pressurization and driving device, water output and discharging pressure shall meet the following requirements, and emergency power source shall be connected.1.Water output: more than 1,200 L/min. Where there are two or more spraying areas, the figure shall be more than 2,000 l/min.2.Discharging pressure: shall enable each water fog nozzle in a spraying area at the farthest end of the piping system to maintain a pressure of more than 2.7kgf/cm2 or 0.27Mpa. But those for protecting electric equipment, the figure shall be more than 3.5kgf/cm2 or 0.35Mpa
中文原文 各類場所消防安全設備設置標準第65條
依前條設置之水源,應連結加壓送水裝置。
加壓送水裝置使用消防幫浦時,其出水量及出水壓力,依下列規定,並連接緊急電源:
一、出水量:每分鐘一千二百公升以上,其放射區域二個以上時為每分鐘二千公升以上。
二、出水壓力:核算管系最末端一個放射區域全部水霧噴頭放水壓力均能達每平方公分二點七公斤以上或0.27MPa以上。
但用於防護電氣設備者,應達每平方公分三點五公斤以上或0.35MPa以上。