Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 59
Outside buildings equipped with automatic sprinkler, 63-mm caliber water flow outlet shall be installed overground near the building line where is accessible for fire fighting cars pursuant to the following provisions:1.They shall be used dedicatedly.2.For a building equipped with automatic sprinkler where the floor area is less than 3,000m2, at least one double-opening outlet shall be installed, and connected to a female quick connector. One more outlet shall be added every time the floor area exceeds 3,000m2. However, if the due number is more than 3, then totally 3 outlets shall be installed.3.They shall be placed where there is no obstacle and the height above the base ground is not more than 1m and not less than 0.5m.4.They shall be connected to standpipe piping system, and their pipe diameters shall be not less than that of standpipe. Moreover, inverted valve and check valve shall be equipped at the locations convenient for examination and repair.5.“Water Outlet” and pressure range shall be marked obviously nearby the outlet.
中文原文 各類場所消防安全設備設置標準第59條
裝置自動撒水之建築物,應於地面層室外臨建築線,消防車容易接近處,設置口徑六十三毫米之送水口,並符合下列規定:
一、應為專用。
二、裝置自動撒水設備之樓層,樓地板面積在三千平方公尺以下,至少設置雙口形送水口一個,並裝接陰式快速接頭,每超過三千平方公尺,增設一個。
但應設數量超過三個時,以三個計。
三、設在無送水障礙處,且其高度距基地地面在一公尺以下零點五公尺以上。
四、與立管管系連通,其管徑在立管管徑以上,並在其附近便於檢修確認處,裝置逆止閥及止水閥。
五、送水口附近明顯易見處,標明自動撒水送水口字樣及送水壓力範圍。
一、應為專用。
二、裝置自動撒水設備之樓層,樓地板面積在三千平方公尺以下,至少設置雙口形送水口一個,並裝接陰式快速接頭,每超過三千平方公尺,增設一個。
但應設數量超過三個時,以三個計。
三、設在無送水障礙處,且其高度距基地地面在一公尺以下零點五公尺以上。
四、與立管管系連通,其管徑在立管管徑以上,並在其附近便於檢修確認處,裝置逆止閥及止水閥。
五、送水口附近明顯易見處,標明自動撒水送水口字樣及送水壓力範圍。