Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 24

Emergency lighting equipments shall be equipped in the following places.1.Living rooms in places used for purposes listed in 12.1, 12.3 and 12.52.Living rooms in places used for purposes listed in 12.2(1), (2), (3) (except school classroom), (4)~(6), residential institutions for psychiatric rehabilitation in (7), (8), (9), and (12).3.Living rooms in buildings with a total floor area amounting to 1,000m2 or more (except school classroom).4.Living rooms in buildings with an effective daylighting area less than 5% of the floor area.5.Aisle, stairway, and passage necessary for escaping from living rooms to refuge, and other proportions need manual lighting in places mentioned in the above 4 clauses.It is allowable that emergency lighting equipments are not equipped where it is recognized by the central regulating authority as a place easy to escape or provided with effective daylighting.
中文原文 各類場所消防安全設備設置標準第24條
下列場所應設置緊急照明設備:
一、供第十二條第一款、第三款及第五款所列場所使用之居室。
二、供第十二條第二款第一目、第二目、第三目(學校教室除外)、第四目至第六目、第七目所定住宿型精神復健機構、第八目、第九目及第十二目所列場所使用之居室。
三、總樓地板面積在一千平方公尺以上建築物之居室(學校教室除外)。
四、有效採光面積未達該居室樓地板面積百分之五者。
五、供前四款使用之場所,自居室通達避難層所須經過之走廊、樓梯間、通道及其他平時依賴人工照明部分。
經中央主管機關認可為容易避難逃生或具有效採光之場所,得免設緊急照明設備。