Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 238

The Disaster Prevention Center shall have a floor area of at least 40 m2 and shall comply with the following:1. The location of the center shall comply with the following subparagraphs:(1) The location shall be easily accessible for firefighters.(2)The location shall be easily accessible for emergency elevators and special refuge stairways.(3) The travel distance between the center exits and any exit that leads outdoors shall be less than 30 meters.2. The construction of the center shall comply with the following:(1) Shall be equipped dedicatedly with air conditioning, such as cooling, heating, and air exchange systems.(2) The disaster monitoring and controlling system and other related equipment shall be fixed firmly into position by anchor bolt or other fixing methods.(3) If the Center has sleeping or resting areas, the areas shall be located in fire compartment.
中文原文 各類場所消防安全設備設置標準第238條
防災中心樓地板面積應在四十平方公尺以上,並依下列規定設置:
一、防災中心之位置,依下列規定:
(一)設於消防人員自外面容易進出之位置。
(二)設於便於通達緊急昇降機間及特別安全梯處。
(三)出入口至屋外任一出入口之步行距離在三十公尺以下。
二、防災中心之構造,依下列規定:
(一)冷暖、換氣等空調系統為專用。
(二)防災監控系統相關設備以地腳螺栓或其他堅固方法予以固定。
(三)防災中心內設有供操作人員睡眠、休息區域時,該部分以防火區劃間隔。

English translation for reference only; the Chinese text prevails. Not legal advice.