Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 218

The configuration of foam outlet, outlet quantity, piping, pressure test, water flow detecting device, starting device and deluge valve of foam fire-suppression equipment, the quantity and concentration of raw foam solution, and the raw foam solution tank shall apply mutais mutandis to the case as referred to in Article 69, 70, 72~74, 78, 79, and 81.The installation of foam outlets used for storage tanks pursuant to Article 213.
中文原文 各類場所消防安全設備設置標準第218條
泡沫滅火設備之泡沫放出口、放射量、配管、試壓、流水檢知裝置、啟動裝置、一齊開放閥、泡沫原液儲存量、濃度及泡沫原液槽設置規定,準用第六十九條、第七十條、第七十二條至第七十四條、第七十八條、第七十九條及第八十一條之規定。
儲槽用之泡沫放出口,依第二百十三條之規定設置。

English translation for reference only; the Chinese text prevails. Not legal advice.