Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 155
Storage batteries shall be used as emergency power source for exit indicating lamp and direction indicating lamp, and the capacity thereof shall be able to ensure the lamp continued illumination for a duration of not less than 20 minutes. However, for the lamps that are installed in the major evacuation routes of the following occupancy, the capacity shall be not less than 60 minutes, and the power source shall adopt both storage batteries and emergency generators.1. Total floor area is 50,000 square meters or more.2. Highrise buildings that have total floor area of 30,000 square meters or more.3. Underground buildings that have total floor area of 1,000 square meters or more.The major evacuation routes provided in the preceding paragraph are as follows:1. Exits that lead outdoors or exits of vestibules, if vestibules exist.2. Exits that lead to stairways or exits of vestibules, if vestibules exist.3. The hallways or passages that lead to exits as prescribed in the preceding subparagraph 1.4. Stairways.
中文原文 各類場所消防安全設備設置標準第155條
出口標示燈及避難方向指示燈之緊急電源應使用蓄電池設備,其容量應能使其有效動作二十分鐘以上。
但設於下列場所之主要避難路徑者,該容量應在六十分鐘以上,並得採蓄電池設備及緊急發電機併設方式:
一、總樓地板面積在五萬平方公尺以上。
二、高層建築物,其總樓地板面積在三萬平方公尺以上。
三、地下建築物,其總樓地板面積在一千平方公尺以上。
前項之主要避難路徑,指符合下列規定者:
一、通往戶外之出入口;設有排煙室者,為該室之出入口。
二、通往直通樓梯之出入口;設有排煙室者,為該室之出入口。
三、通往第一款出入口之走廊或通道。
四、直通樓梯。
但設於下列場所之主要避難路徑者,該容量應在六十分鐘以上,並得採蓄電池設備及緊急發電機併設方式:
一、總樓地板面積在五萬平方公尺以上。
二、高層建築物,其總樓地板面積在三萬平方公尺以上。
三、地下建築物,其總樓地板面積在一千平方公尺以上。
前項之主要避難路徑,指符合下列規定者:
一、通往戶外之出入口;設有排煙室者,為該室之出入口。
二、通往直通樓梯之出入口;設有排煙室者,為該室之出入口。
三、通往第一款出入口之走廊或通道。
四、直通樓梯。