Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 146-1

┌────────────┬────────┬────────┐│ Classification │Vertical │ Luminous ││ │dimension of the│ intensity of ││ │lamp face (m) │ the lamp face ││ │ │ (cd) │├──────┬─────┼────────┼────────┤│Exit │Class A │Over 0.4 │ Over 50 ││indicating │ │(inclusive) │ (inclusive) ││lamp ├─────┼────────┼────────┤│ │Class B │0.2~0.4 │ Over 10 ││ │ │(not inclusive) │ (inclusive) ││ ├─────┼────────┼────────┤│ │Class C │0.1~0.2 │ Over 1.5 ││ │ │(not inclusive) │ (inclusive) │├──────┼─────┼────────┼────────┤│Direction │Class A │Over 0.4 │ Over 60 ││indicating │ │(inclusive) │ (inclusive) ││lamp ├─────┼────────┼────────┤│ │Class B │0.2~0.4 │ Over 13 ││ │ │(not inclusive) │ (inclusive) ││ ├─────┼────────┼────────┤│ │Class C │0.1~0.2 │ Over 5 ││ │ │(not inclusive) │ (inclusive) │└──────┴─────┴────────┴────────┘
中文原文 各類場所消防安全設備設置標準第146-1條
出口標示燈及非設於樓梯或坡道之避難方向指示燈,其標示面縱向尺度及光度依等級區分如下:┌─────────┬───────────┬────────┐│區分│標示面縱向尺度(m)│標示面光度(cd)│├──────┬──┼───────────┼────────┤││A級│零點四以上│五十以上││├──┼───────────┼────────┤│出口標示燈│B級│零點二以上,未滿零點四│十以上││├──┼───────────┼────────┤││C級│零點一以上,未滿零點二│一點五以上│├──────┼──┼───────────┼────────┤││A級│零點四以上│六十以上││避難方向指示├──┼───────────┼────────┤│燈│B級│零點二以上,未滿零點四│十三以上││├──┼───────────┼────────┤││C級│零點一以上,未滿零點二│五以上│└──────┴──┴───────────┴────────┘