Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 142
Gas leakage signal receiving switchboard shall meet the following requirements:1.Gas leakage signal receiving switchboard shall be located in watchroom or other populated places. Where a disaster prevention center is set up, the switchboard shall be located in the center.2.The alarm division where gas leakage occurs shall be marked.3.For detectors installed at the position the gas pipe goes through the wall, the alarm divisions shall be marked respectively.4.The operating switch of wall-mounting switchboard shall be 0.8m~1.5m high from the floor (0.6~1.5m for seat type)5.The tone color and volume of the main sound device shall be different from other alarm sounds.6.Where there are two or more gas leakage signal receiving switchboards in a same building, equipments for communication between the two shall be installed at the switchboards.
中文原文 各類場所消防安全設備設置標準第142條
瓦斯漏氣受信總機,依下列規定:
一、裝置於值日室等平時有人之處所。
但設有防災中心時,設於該中心。
二、具有標示瓦斯漏氣發生之警報分區。
三、設於瓦斯導管貫穿牆壁處之檢知器,其警報分區應個別標示。
四、操作開關距樓地板面之高度,須在零點八公尺以上(座式操作者為零點六公尺)一點五公尺以下。
五、主音響裝置之音色及音壓應有別於其他警報音響。
六、一棟建築物內有二臺以上瓦斯漏氣受信總機時,該受信總機處,設有能相互同時通話連絡之設備。
一、裝置於值日室等平時有人之處所。
但設有防災中心時,設於該中心。
二、具有標示瓦斯漏氣發生之警報分區。
三、設於瓦斯導管貫穿牆壁處之檢知器,其警報分區應個別標示。
四、操作開關距樓地板面之高度,須在零點八公尺以上(座式操作者為零點六公尺)一點五公尺以下。
五、主音響裝置之音色及音壓應有別於其他警報音響。
六、一棟建築物內有二臺以上瓦斯漏氣受信總機時,該受信總機處,設有能相互同時通話連絡之設備。