Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 138
Audio amplifier and operating device shall comply with CNS No.10522, and installed pursuant to the following provisions:1.Operating device shall be interlocked with actuating device or automatic fire alarm equipment, and marked with the storeys or the area covered by the operating of the actuating device or automatic fire alarm equipment.2.Functions of selecting necessary storeys or areas shall be provided.3.Signals indicating short circuit shall be provided where the wiring of a broadcasting division is in short.4.The operating switch of operating device shall be 0.6~1.5m above the floor (0.6~1.5m for seat type).5.Operating device shall be located in watchroom or other usually populated places. Where a disaster prevention center is set up, the switchboard shall be located in the center.
中文原文 各類場所消防安全設備設置標準第138條
擴音機及操作裝置,應符合CNS一○五二二之規定,並依下列規定設置:
一、操作裝置與啟動裝置或火警自動警報設備動作連動,並標示該啟動裝置或火警自動警報設備所動作之樓層或區域。
二、具有選擇必要樓層或區域廣播之性能。
三、各廣播分區配線有短路時,應有短路信號之標示。
四、操作裝置之操作開關距樓地板面之高度,在零點八公尺以上(座式操作者,為零點六公尺)一點五公尺以下。
五、操作裝置設於值日室等經常有人之處所。
但設有防災中心時,設於該中心。
一、操作裝置與啟動裝置或火警自動警報設備動作連動,並標示該啟動裝置或火警自動警報設備所動作之樓層或區域。
二、具有選擇必要樓層或區域廣播之性能。
三、各廣播分區配線有短路時,應有短路信號之標示。
四、操作裝置之操作開關距樓地板面之高度,在零點八公尺以上(座式操作者,為零點六公尺)一點五公尺以下。
五、操作裝置設於值日室等經常有人之處所。
但設有防災中心時,設於該中心。