Standard for Installation of Fire Safety Devices based on Use and Occupancy Article 136

Actuating device of emergency broadcasting equipments shall comply with CNS No.10522, and be installed pursuant to the following provisions:1.The travel distance from any point of each floor to the actuating device shall be less than 50m.2.Actuating device shall be installed within 0.8m~1.5m above the floor.3.Emergency telephone starting shall be used for storeys above the 11th floor, or under the 3rd floor or underground storeys.
中文原文 各類場所消防安全設備設置標準第136條
緊急廣播設備之啟動裝置應符合CNS一○五二二之規定,並依下列規定設置:
一、各樓層任一點至啟動裝置之步行距離在五十公尺以下。
二、設在距樓地板高度零點八公尺以上一點五公尺以下範圍內。
三、各類場所第十一層以上之各樓層、地下第三層以下之各樓層或地下建築物,應使用緊急電話方式啟動。